Variable frequency drive motor feed. (VFD) For Alternating Current (50/60Hz), for three-phase systems (380/190V) and systems with voltages up to 1kV. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried.
Standard | ||
---|---|---|
Sheath | Conductors | |
3 Conductors |
The information provided corresponds to the standard version, and different alternatives of insulation and / or covering materials can be used upon request.
Nominal cross-section sq (mm²) | Nominal cross-section Concentric conductor sq mm | Electrical resistance at 20°C in C.C. Ohm/km | Electrical resistance at 20°C in C.C. Concentric conductor Ohm/km | Electrical resistance at 90°C in C.C. Ohm/km | Electrical resistance at 90°C in C.C. Concentric conductor Ohm/km | Inductive reactance at 50Hz (Ohm/Km) | Current-carrying capacity of cables in free air at 40°C as per IEC 364-5-523. Cables displayed in Cable Ladder or perforated tray. (Ampere) | Current-carrying capacity of cables directly buried at 25°C soil temperature and soil thermal resistance of 1 km/W as per IEC 364-5-523. (Ampere) |
---|---|---|---|---|---|---|---|---|
1.5 | 0.5 | 13.3 | 39 | 16.96 | 49.73 | 0.1 | 20 | 28 |
2.5 | 0.5 | 7.98 | 39 | 10.18 | 49.73 | 0.093 | 28 | 37 |
4 | 0.5 | 4.95 | 39 | 6.31 | 49.73 | 0.088 | 36 | 48 |
6 | 0.75 | 3.3 | 26 | 4.21 | 33.15 | 0.083 | 47 | 61 |
10 | 1 | 1.91 | 19.5 | 2.44 | 24.86 | 0.078 | 65 | 83 |
16 | 1.5 | 1.21 | 13.3 | 1.54 | 16.96 | 0.075 | 86 | 107 |
25 | 2.5 | 0.78 | 7.98 | 0.99 | 10.18 | 0.075 | 109 | 141 |
35 | 4 | 0.554 | 4.95 | 0.707 | 6.31 | 0.073 | 137 | 168 |
50 | 6 | 0.386 | 3.3 | 0.493 | 4.21 | 0.073 | 166 | 199 |
70 | 10 | 0.272 | 1.91 | 0.348 | 2.44 | 0.071 | 213 | 243 |
95 | 10 | 0.206 | 1.91 | 0.264 | 2.44 | 0.07 | 257 | 293 |
120 | 16 | 0.161 | 1.21 | 0.207 | 1.54 | 0.07 | 299 | 333 |
150 | 16 | 0.129 | 1.21 | 0.167 | 1.54 | 0.07 | 345 | 373 |
185 | 25 | 0.106 | 0.78 | 0.138 | 0.99 | 0.07 | 394 | 425 |
240 | 25 | 0.0801 | 0.78 | 0.106 | 0.99 | 0.069 | 465 | 493 |
300 | 35 | 0.0641 | 0.554 | 0.086 | 0.707 | 0.069 | 537 | 559 |
Cable Formation, N° Cond. x cross-section (mm²) | Diameter under shield mm | External diameter mm | Weight kg/km | Code |
---|---|---|---|---|
3 x 1.5 | 9 | 12.3 | 213 | BX 0315 /10 |
3 x 2.5 | 9.3 | 12.7 | 239 | BX 0325 /10 |
3 x 4 | 10.3 | 13.6 | 300 | BX 0340 /10 |
3 x 6 | 11.7 | 15 | 382 | BX 0360 /10 |
3 x 10 | 14 | 17.3 | 551 | BX 3100 /10 |
3 x 16 | 16 | 19.4 | 749 | BX 3160 /10 |
3 x 25 | 19.5 | 22.9 | 1,105 | BX 3250 /10 |
3 x 35 | 21.7 | 25.1 | 1,431 | BX 3350 /10 |
3 x 50 | 25.1 | 28.5 | 1,930 | BX 3500 /10 |
3 x 70 | 31.3 | 35.1 | 2,746 | BX 3700 /10 |
3 x 95 | 35.6 | 39.6 | 3,520 | BX 3950 /10 |
3 x 120 | 39.1 | 43.3 | 4,427 | BX 31200 /10 |
3 x 150 | 45.1 | 49.7 | 5,551 | BX 31500 /10 |
3 x 185 | 49 | 53.8 | 6,706 | BX 31850 /10 |
3 x 240 | 56.3 | 61.3 | 8,717 | BX 32400 /10 |
3 x 300 | 62.7 | 68.1 | 10,849 | BX 33000 /10 |