LSZH series BX C 10

0.6/1kV
Flexible Cu 1.5 up to 300mm²
XLPE 90°C / LSZH
Shield: 10% coverage

Variable frequency drive motor feed (VFD) in closed environments with a high concentration of people or in locations with equipment sensitive to exposure to corrosive gases. For Alternating Current (50/60Hz), for three-phase systems (380/190V) and systems with voltages up to 1kV. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried.

Features

  • Temperature rating: 90ºC (operating), 130ºC (overload), 250ºC (short circuit)

  • Voltage rating: 600/1000V AC, maximum 1200V AC / 1500V DC

  • Construction requirements: As per IRAM 2178-1 – IEC 60502-1

  • Conductor requirements: As per IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: XLPE (Crosslinked polyethylene)

  • Bedding: LSZH

  • Shield: Composed by a concentric conductor made of copper tape and/or copper wires, with a shilelding cross-section of 10% of the phase of each cable model

  • Sheath: LSZH-HFFR (Low Smoke Zero Halogen - Halogen Free Flame Retardant), flame retardant, sunlight, and oil resistant

  • Fire requirements: As per ICEA T 30-520

  • Standard for halogen absence and corrosive gases: As per IEC 60754-1/2

  • Smoke transparency requirements: As per IEC 61034-1/2

  • Toxicity standard: As per NES 713 – CEI 20.37

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (UV rays)

  • Water behaviour requirements: Suitable AD7 (Occasional water submersion)

Electromagnetic interference protection

Electromagnetic interference protection

Fire-retardant

Fire-retardant

Halogen free

Halogen free

Low smoke

Low smoke

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Identification

Standard
Sheath Conductors
3 Conductors

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

ELECTRICAL CHARACTERISTICS

Resistances, reactance and intensity of admissible currents

Nominal cross-section sq (mm²) Nominal cross-section Concentric conductor sq mm Electrical resistance at 20°C in C.C. Ohm/km Electrical resistance at 20°C in C.C. Concentric conductor Ohm/km Electrical resistance at 90°C in C.C. Ohm/km Electrical resistance at 90°C in C.C. Concentric conductor Ohm/km Inductive reactance at 50Hz (Ohm/Km) Current-carrying capacity of cables in free air at 40°C as per IEC 364-5-523. Cables displayed in Cable Ladder or perforated tray. (Ampere) Current-carrying capacity of cables directly buried at 25°C soil temperature and soil thermal resistance of 1 km/W as per IEC 364-5-523. (Ampere)
1.50.513.33916.9649.730.12028
2.50.57.983910.1849.730.0932837
40.54.95396.3149.730.0883648
60.753.3264.2133.150.0834761
1011.9119.52.4424.860.0786583
161.51.2113.31.5416.960.07586107
252.50.787.980.9910.180.075109141
3540.5544.950.7076.310.073137168
5060.3863.30.4934.210.073166199
70100.2721.910.3482.440.071213243
95100.2061.910.2642.440.07257293
120160.1611.210.2071.540.07299333
150160.1291.210.1671.540.07345373
185250.1060.780.1380.990.07394425
240250.08010.780.1060.990.069465493
300350.06410.5540.0860.7070.069537559

DIMENSIONS & WEIGHT

Cable Formation, N° Cond. x cross-section (mm²) Diameter under shield mm External diameter mm Weight kg/km Code
3 x 1.5912.3213BX 0315 C/10
3 x 2.59.312.7239BX 0325 C/10
3 x 410.313.6300BX 0340 C/10
3 x 611.715382BX 0360 C/10
3 x 101417.3551BX 3100 C/10
3 x 161619.4749BX 3160 C/10
3 x 2519.522.91,105BX 3250 C/10
3 x 3521.725.11,431BX 3350 C/10
3 x 5025.128.51,930BX 3500 C/10
3 x 7031.335.12,746BX 3700 C/10
3 x 9535.639.63,520BX 3950 C/10
3 x 12039.143.34,427BX 31200 C/10
3 x 15045.149.75,551BX 31500 C/10
3 x 1854953.86,706BX 31850 C/10
3 x 24056.361.38,717BX 32400 C/10
3 x 30062.768.110,849BX 33000 C/10