series CX

600 Volt
Cu 14 up to 10 AWG
XHHW-2
UL 1277

Control, signalling, measuring and protective equipment; electric controls of industrial installations. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. Manufactured in compliance with the National Electrical Code ANSI/NFPA 70 of the US and the National Electrical Code NOM-001 SEDE, Mexico.

Features

  • Temperature rating: 90ºC (operating), 130ºC (overload), 250ºC (short circuit)

  • Voltage rating: 600V AC

  • Construction requirements: As per UL 1277

  • Conductor requirements: As per ASTM B8

  • Conductor: Annealed electrolytic copper conductor, class B stranding

  • Insulation: XLPE (Crosslinked polyethylene) type XHHW-2

  • Sheath: Flame retardant PVC

  • Fire requirements: As per UL 1685

  • Outdoors requirements: As per UL 2556 (UV rays)

  • NEC code (NFPA 70): Art. 336 TC –Art. 501 classified areas CL1 Div.2 y Cl2 Div.2

Fire-retardant

Fire-retardant

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Industrial applications

Industrial applications

NEC cod

NEC cod

Tray cable

Tray cable

Identification

Standard
Sheath Conductors
Multiconductor alphanumeric identification

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version. Upon request, we can supply cables with different alternatives of identification, cable flexibility, or also including additional shield for suitable electromagnetic protection.

ELECTRICAL CHARACTERISTICS

Calibre AWG Electrical resistance at 20°C in C.C. (Ohm/km) Electrical resistance at 90°C in C.A. at 60Hz (Ohm/km) Current-carrying capacity (1)
2x 4x 7x 10x 19x 30x 48x
148.7911.21252017.512.512.511.38.8
125.547.06302421151513.510.5
103.484.4440322820201814

(1) Current-carrying capacity of cables with up to three conductors, installed in ducts or directly buried, up to an ambient temperature of 30ºC, according to chart 310.15 (B)(16) of the NFPA 70. As from four-conductors, we’ve additionally applied the correction factor for more than three conductors from the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x gauge AWG External diameter mm Weight kg/km Code
2x149.0116CX 0214
3x149.5139CX 0314
4x1410.4168CX 0414
5x1411.4199CX 0514
7x1412.4256CX 0714
10x1416.3357CX 1014
12x1416.8411CX 1214
14x1418.0470CX 1414
16x1419.0527CX 1614
19x1420.0613CX 1914
21x1422.1721CX 2114
24x1424.1815CX 2414
27x1424.6896CX 2714
30x1425.8984CX 3014
32x1426.71045CX 3214
37x1427.81186CX 3714
48x1431.31500CX 4814
2x1210.0154CX 0212
3x1210.6188CX 0312
4x1211.6230CX 0412
5x1212.7274CX 0512
7x1214.6382CX 0712
10x1218.2495CX 1012
12x1218.8574CX 1212
14x1220.1660CX 1412
16x1222.3793CX 1612
19x1223.4921CX 1912
21x1224.71008CX 2112
24x1226.91144CX 2412
27x1227.51263CX 2712
30x1228.91390CX 3012
32x1230.01476CX 3212
37x1231.11683CX 3712
48x1235.22141CX 4812
2x1011.2211CX 0210
3x1011.9263CX 0310
4x1013.1325CX 0410
5x1015.1414CX 0510
7x1016.4542CX 0710
10x1020.6708CX 1010
12x1022.2877CX 1210
14x1023.81007CX 1410
16x1025.11133CX 1610
19x1026.51324CX 1910
21x1027.91453CX 2110
24x1030.51650CX 2410
27x1031.21829CX 2710
30x1032.82017CX 3010
32x1034.02144CX 3210
37x1035.42456CX 3710
48x1040.13136CX 4810