series FM

0.6/1kV
Flexible Cu 1 up to 4mm²
Up to 48 Conductors
XLPE 90°C / LSZH

Control, signalling, measuring and protective equipment, electric controls of home installations. Use in closed environments with a high concentration of people (airports, hospitals, trains, cinemas, shopping centers, tunnels) and in control rooms with electronic equipment sensitive to the exposure of corrosive gases. Installed in conduits, trays, cable ladders, in direct open air or indoors, buried in a trench or in ducts.

Features

  • Temperature rating: 90ºC (operating),130ºC (overload) and 250ºC (short circuit)

  • Voltage rating: 600/1000V AC, maximum 1200V AC / 1500V DC

  • Construction requirements: As per IRAM 2178-1 – IEC 60502-1

  • Conductor requirements: As per IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: XLPE (Cross-linked polyethylene)

  • Sheath: LSZH-HFFR (Low Smoke Zero Halogen - Halogen Free Flame Retardant), fire-retardant; sunlight and oils resistant

  • Fire requirements: As per IEC 60332-3-24

  • Standard for halogen absence and corrosive gases: As per IEC 60754-1/2

  • Smoke transparency requirements: As per IEC 61034-1/2

  • Toxicity standard: As per NES 713 – CEI 20.37

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (UV rays)

  • Water behaviour requirements: Suitable AD7 (Occasional water submersion)

Fire-retardant

Fire-retardant

Halogen free

Halogen free

Low smoke

Low smoke

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Water immersion

Water immersion

Identification

Standard
Sheath Conductors
Multiconductors alphanumeric identification

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of insulation and / or covering materials can be used upon request.

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Nominal cross-section sq mm² Electrical resistance at 20ºC in C.C Ohm/km Electrical resistance at 90ºC in C.A. Ohm/km Current-carrying capacity in free air. At 40°C as per IEC 364-5-523. Formations in perforated trays or ladder type. (Ampere)
2x 4x 7x 10x 19x 30x 48x
119.524.86--------------
1.513.316.96232016.111.511.510.48.1
2.57.9810.18312821.715.515.514.010.9
44.956.31433630.121.521.519.4--

As from seven-conductors, we’ve additionally applied the correction factor for more than three conductors the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable formation N° Cond. x cross-section (mm²) External diameter mm Weight kg/km Code
2x18.286FM 0210
3x18.698FM 0310
4x19.3114FM 0410
5x110.0133FM 0510
7x110.8160FM 0710
10x114.2235FM 1010
12x114.6262FM 1210
14x115.3291FM 1410
19x116.8362FM 1910
24x119.4444FM 2410
30x120.5523FM 3010
37x122.0617FM 3710
48x125.0772FM 4810
2x1.58.7102FM 0215
3x1.59.2117FM 0315
4x1.59.9138FM 0415
5x1.510.7163FM 0515
7x1.511.6199FM 0715
10x1.515.2288FM 1015
12x1.515.7324FM 1215
14x1.516.4362FM 1415
19x1.518.1457FM 1915
24x1.520.9562FM 2415
30x1.522.1668FM 3015
37x1.523.8795FM 3715
48x1.527.11001FM 4815
2x2.59.6132FM 0225
3x2.510.1155FM 0325
4x2.511.0185FM 0425
5x2.511.9221FM 0525
7x2.512.9275FM 0725
10x2.516.9391FM 1025
12x2.517.5445FM 1225
14x2.518.3502FM 1425
19x2.520.2642FM 1925
24x2.523.5795FM 2425
30x2.524.9956FM 3025
37x2.526.81146FM 3725
48x2.530.91468FM 4825
2x410.7175FM 0240
3x411.3210FM 0340
4x412.3254FM 0440
5x413.3306FM 0540
7x414.5387FM 0740
10x419.1542FM 1040
12x419.7623FM 1240
14x420.7709FM 1440
19x422.9918FM 1940
24x426.71143FM 2440
30x428.51400FM 3040
37x430.81687FM 3740