Clad series RPBS

Steel wire armour

0.6/1kV
Flexible Cu 1 up to 400mm²
Insulation (MICA+XLPE)
Increased integrity

Extended performance to preserve electrical integrity in direct fire conditions. This is verified in different tests where the cable is exposed to direct fire for 3 hours at 950ºC, direct fire and water spray, and direct fire and mechanical shock simulated by repetitive striking. For fixed power distribution networks for alternating current (50/60Hz), for single-phase systems (220/110V), three-phase systems (380/190V) and systems with voltages up to 1kV. For Direct Current, used in systems with voltages up to 1.5kV Use in closed environments with a high concentration of people (airports, hospitals, trains, cinemas, shopping centers, tunnels) and in control rooms with electronic equipment sensitive to the exposure of corrosive gases. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried.

Features

  • Temperature ratings: 90°C (Operating) – 130°C (Overload) – 250°C (Short-Circuit)

  • Voltage rating: 600/1000 Volt A.C. – 1200 Volt A.C. (Max) – 1500 Volt D.C.

  • Construction requirements: IRAM 62266 – IEC 60502-1

  • Conductor requirements: IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: Mica tape + XLPE (Cross-Linked Polyethylene)

  • Taping on assembled conductors: Fire penetration blocking material

  • Bedding: LSZH-HFFR (Low Smoke Zero Halogen - Halogen Free Flame Retardant)

  • Armour: Single conductor cables with double aluminum tape. Multiconductor cables galvanized steel wire armour. The use of armoured single conductor cables in A.C. systems, requires the armour to be of a non-magnetic material.

  • Sheath: LSZH-HFFR (Low Smoke Zero Halogen - Halogen Free Flame Retardant), flame retardant, sunlight, and oil resistant

  • Fire requirements: As per IEC 60332-3-24

  • Fire resistance standards: As per IEC 60331-21 (70000 BTU-750°C applied for 90 minutes)

  • Additional fire resistance standards: BS 6387 standard:Category C: Direct fire for 3 hours at 950ºC.Category W: Direct Fire for 15 minutes at 650ºC + later water spray for 15 minutes. Category Z: Direct fire for 15 minutes at 950ºC + mechanical shocks every 30 seconds on the metal clamp.IEC 60331-1/2 standard: Direct fire for 2 hours at 830ºC + mechanical shocks every 5 minutes on the metal clamp.

  • Standard for Halogen absence and corrosive gases: IEC 60754-1/2

  • Smoke transparency requirements: IEC 61034-1/2

  • Toxicity standard: NES 713 – CEI 20.37

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (UV rays)

  • Water behaviour requirements: Suitable for AD7 (Occasional water submersion)

Fire-retardant

Fire-retardant

Fire-resistant

Fire-resistant

Halogen free

Halogen free

Low smoke

Low smoke

UV resistant

UV resistant

Water pump

Water pump

Identification

Standard
Sheath Conductors
Unipolar
Bipolar
Tripolar
Tetrapolar

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

ELECTRICAL CHARACTERISTICS

Resistances and reactance

Nominal cross-section (mm²) Electrical resistance in D.C. at 20°C (Ohm/km) Electrical resistance in C.C. at 90°C (Ohm/km) Inductive reactance at 50Hz (Ohm/Km)
1 Conductor (1) 1 Conductor (2) 1 Conductor (3) Multiconductor (4) 4 Conductors (5)
119.524.86------0.1290.136
1.513.316.96------0.1190.127
2.57.9810.18------0.1100.117
44.956.31------0.1040.111
63.34.21------0.0960.104
101.912.44------0.0900.098
161.211.540.1430.1860.1280.0860.093
250.780.990.1350.1780.1200.0830.090
350.5540.7070.1290.1730.1150.0800.088
500.3860.4930.1250.1680.1100.0790.086
700.2720.3480.1180.1620.1040.0760.084
950.2060.2640.1130.1570.0990.0740.081
1200.1610.2070.1130.1570.0990.0740.081
1500.1290.1670.1090.1530.0950.0730.080
1850.1060.1380.1090.1520.0940.0730.080
2400.08010.1060.1050.1490.0910.0720.079
3000.06410.08600.1030.1470.0880.0710.079
4000.04860.06750.1010.1450.087----

(1) Three single conductor cables displayed in flat, in contact with each other. (2) Three single conductor cables displayed in flat, separated by 1 diameter between each other. (3) Three single-conductor cables displayed in a trefoil in contact with each other. (4) Calculation of Inductive reactance valid for two-conductor and three conductor cables. (5) Calculation of Inductive reactance valid for four-conductor cables.

Intensity of admissible currents

Nominal cross-section (mm²) Current-carrying capacity of cables in free air at 40°C as per IEC 364-5-523.Single-conductors cable up to 16mm² in contact with each other, displayed in unperforated trays, remaining cross-sections, single-conductors displays and formations in cable ladder or perforated cable trays (Ampere) Current-carrying capacity of cables directly buried at 25°C soil temperature and soil thermal resistance of 1 km/W as per IEC 364-5-523 (Ampere)
1 Conductor (1) 1 Conductor (2) 1 Conductor (3) 2 Conductors Multiconductor (4) 1 Conductor (1) 1 Conductor (2) 2 Conductors Multiconductor (4)
1------------------
1.519----232032353228
2.526----312843464437
434----433655595748
645----544769747261
1062----7465931009783
1683----10086121129129107
25122158117128109157168166141
35152196146160137188201200168
50187238179195166220236238199
70241305232250213271290292243
95295371283304257326349351293
120346432332354299371396399333
150401499384409345415444448373
185461572441468394470503508425
240548675524554465547586592493
300637780608640537621665669559
400751938712----710759----

(1) Three single conductor cables displayed in flat, in contact with each other. (2) Three single conductor cables displayed in flat, separated by 1 diameter between each other. (3) Three single-conductor cables displayed in a trefoil in contact with each other. (4) The values of current-carrying capacity informed, correspond to three-conductor, four-conductor.

DIMENSIONS & WEIGHT

Cable formation N° Cond. x cross-section (mm²) Diameter below armour mm External diameter mm Weight kg/km Code
1 x 1610.315.2379RPBS 1160 D
1 x 2511.616.5488RPBS 1250 D
1 x 3512.617.5595RPBS 1350 D
1 x 5014.319.4771RPBS 1500 D
1 x 7016.521.6999RPBS 1700 D
1 x 9518.523.61,229RPBS 1950 D
1 x 12020.226.21,575RPBS 11200 D
1 x 15022.528.51,880RPBS 11500 D
1 x 18524.430.62,227RPBS 11850 D
1 x 24027.634.02,824RPBS 12400 D
1 x 30030.837.23,443RPBS 13000 D
1 x 40035.041.84,448RPBS 14000 D
2 x 110.014.6340RPBS 0210 H
2 x 1.510.515.1362RPBS 0215 H
2 x 2.511.416.0406RPBS 0225 H
2 x 412.417.0460RPBS 0240 H
2 x 613.618.2531RPBS 0260 H
2 x 1016.021.5844RPBS 2100 H
2 x 1618.023.51022RPBS 2160 H
2 x 2520.827.01451RPBS 2250 H
2 x 3522.829.01,714RPBS 2350 H
2 x 5026.132.32,130RPBS 2500 H
2 x 7030.537.12,722RPBS 2700 H
2 x 9534.942.83,741RPBS 2950 H
2 x 12038.246.34,429RPBS 21200 H
2 x 15043.051.35,211RPBS 21500 H
2 x 18547.156.86,638RPBS 21850 H
2 x 24053.463.78,334RPBS 22400 H
2 x 30060.270.79,993RPBS 23000 H
3 x 110.615.2376RPBS 0310 H
3 x 1.511.215.8404RPBS 0315 H
3 x 2.512.216.8459RPBS 0325 H
3 x 413.217.8530RPBS 0340 H
3 x 614.519.1622RPBS 0360 H
3 x 1017.122.6992RPBS 3100 H
3 x 1619.324.81228RPBS 3160 H
3 x 2522.228.41,758RPBS 3250 H
3 x 3524.430.62,118RPBS 3350 H
3 x 5028.034.42,696RPBS 3500 H
3 x 7033.140.83,901RPBS 3700 H
3 x 9537.445.54,746RPBS 3950 H
3 x 12041.149.45,696RPBS 31200 H
3 x 15046.656.37,366RPBS 31500 H
3 x 18550.660.38,508RPBS 31850 H
3 x 24057.968.410,879RPBS 32400 H
4 x 111.616.2422RPBS 0410 H
4 x 1.512.216.8456RPBS 0415 H
4 x 2.513.317.9525RPBS 0425 H
4 x 414.519.1613RPBS 0440 H
4 x 616.021.5890RPBS 0460 H
4 x 1018.924.41164RPBS 4100 H
4 x 1621.327.51630RPBS 4160 H
3 x 25 + 1 x 1623.8301,986RPBS 2516 H
3 x 35 + 1 x 1625.631.82,330RPBS 3516 H
3 x 50 + 1 x 2529.535.93,003RPBS 5025 H
3 x 70 + 1 x 3534.442.34,323RPBS 7035 H
3 x 95 + 1 x 5039.147.25,302RPBS 9550 H
3 x 120 + 1 x 7043.451.96,503RPBS 12070 H
3 x 150 + 1 x 7048.157.88,124RPBS 15070 H
3 x 185 + 1 x 9552.762.69,523RPBS 18595 H
3 x 240 + 1 x 12059.970.612,154RPBS 240120 H