Block series CY-A

Helically shielded with aluminium/polyester tape

600 Volt
Cu 14 up to 10 AWG
Double insulation
UL 1277

Control, signalling, measuring and protective equipment; electric controls of industrial installations. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It provides additional electromagnetic protection. Manufactured in compliance with the National Electrical Code ANSI/NFPA 70 of the US and the National Electrical Code NOM-001 SEDE, Mexico.

Features

  • Temperature rating: 90ºC (operating), 160ºC (short circuit)

  • Voltage rating: 600V AC

  • Construction requirements: As per UL 1277

  • Conductor requirements: As per ASTM B8

  • Conductor: Annealed electrolytic copper; class B

  • Primary insulation: Special PVC compound

  • Secondary insulation: THHN (Nylon)

  • Shield: Helically applied Aluminium – Polyester tape plus tinned copper drain wire

  • Sheath: PVC, fire-retardant

  • Fire requirements: As per UL 1685

  • Test requirements: As per UL 2556 (UV rays)

  • NEC code (NFPA 70): Art 336 - Art 501 classified areas Cl 1 Div 2 and Cl 2 Div 2

Electromagnetic interference protection

Electromagnetic interference protection

Fire-retardant

Fire-retardant

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Industrial applications

Industrial applications

Wet locations

Wet locations

Identification

Standard
Sheath Conductors
Multiconductor alphanumeric identification

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Gauge AWG Electrical resistance at 20°C in C.C.  (Ohm/km) Electrical resistance at 90°C in C.A. at 60Hz (Ohm/km) Current-carrying capacity (1)
2x 4x 7x 10x 19x 30x 48x
148.7911.21252017.512.512.511.38.8
125.547.06302421151513.510.5
103.484.4440322820201814

(1) Current-carrying capacity of cables with up to three conductors, installed in ducts or directly buried, up to an ambient temperature of 30ºC, according to chart 310.15 (B)(16) of the NFPA 70. As from four-conductors, we’ve additionally applied the correction factor for more than three conductors from the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x gauge AWG Diameter under shield mm External diameter mm Weight kg/km Code
2 x 145.78.296CY 0214 A
3 x 146.18.6122CY 0314 A
4 x 146.99.4151CY 0414 A
5 x 147.610.2180CY 0514 A
7 x 148.511.0234CY 0714 A
10 x 1411.014.3345CY 1014 A
12 x 1411.514.7397CY 1214 A
14 x 1412.515.8453CY 1414 A
19 x 1414.117.4589CY 1914 A
24 x 1416.720.0730CY 2414 A
30 x 1418.122.4938CY 3014 A
37 x 1419.824.11129CY 3714 A
48 x 1422.827.11428CY 4814 A
2 x 126.69.1126CY 0212 A
3 x 127.19.7166CY 0312 A
4 x 128.010.5207CY 0412 A
5 x 128.911.5249CY 0512 A
7 x 129.912.5329CY 0712 A
10 x 1212.916.2484CY 1012 A
12 x 1213.416.7561CY 1212 A
14 x 1214.617.9643CY 1412 A
19 x 1216.519.8845CY 1912 A
24 x 1219.523.81106CY 2412 A
30 x 1221.225.51344CY 3012 A
37 x 1223.227.51629CY 3712 A
48 x 1226.630.92071CY 4812 A
2 x 108.410.9180CY 0210 A
3 x 109.011.5242CY 0310 A
4 x 1010.112.6306CY 0410 A
5 x 1011.314.6396CY 0510 A
7 x 1012.515.8523CY 0710 A
10 x 1016.319.6727CY 1010 A
12 x 1016.920.2849CY 1210 A
14 x 1018.422.71029CY 1410 A
19 x 1020.925.21351CY 1910 A
24 x 1024.729.01683CY 2410 A
30 x 1026.831.12057CY 3010 A
37 x 1029.233.62504CY 3710 A
48 x 1033.637.93197CY 4810 A