Clad series EF-F

Steel tape armour

0.6/1kV
Flexible Cu 2.5 up to 630mm²
XLPE 90°C / LSZH
No PE conductor

Fixed power distribution networks in closed environments with a high concentration of people (airports, hospitals, trains, cinemas, shopping malls, tunnels) and in control rooms with electronic equipment sensitive to exposure to corrosive gases. For Alternating Current (50/60Hz), for single-phase systems (220/110V), three-phase systems (380/190V) and systems with voltages up to 1kV. For Direct Current, used in systems with voltages up to 1.5kV Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It has additional mechanical protection.

Features

  • Temperature rating: 90ºC (operating),130°C (overload) and 250°C (short circuit)

  • Voltage rating: 600/1000V AC, maximum 1200V AC / 1500V CC

  • Construction requirements: As per IRAM 62266 – IEC 60502-1

  • Conductor requirements: As per IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: XLPE (crosslinked polyethylene)

  • Bedding: LSZH-HFFR (Low Smoke Zero Halogen - Halogen Free Flame Retardant)

  • Armour: Double aluminium tape spiral wrap (in single-conductor cables) and double galvanized steel helical tape. The use of armored single core cables in A.C. requires that the armature be of a non-magnetic material.

  • Sheath: LSZH-HFFR (Low Smoke Zero Halogen - Halogen Free Flame Retardant) flame retardant, sunlight, and oil resistant

  • Fire requirements: As per IEC 60332-3-24

  • Standard for halogen absence and corrosive gases: As per IEC 60754-1/2

  • Smoke transparency requirements: IEC 61034-1/2

  • Toxicity standard: NES 713 – CEI 20.37

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (UV rays)

  • Water behaviour requirements: Suitable AD7 (Occasional water submersion)

Fire-retardant

Fire-retardant

Halogen free

Halogen free

Low smoke

Low smoke

Flexible stranded conductors

Flexible stranded conductors

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Identification

Standard
Sheath Conductors
1 Conductor
2 Conductors
3 Conductors
4 Conductors

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of insulation and / or covering materials can be used upon request.

ELECTRICAL CHARACTERISTICS

Resistances and reactance

Nominal cross-section sq (mm²) Electrical resistance in D.C. at 20°C (Ohm/km) Electrical resistance in C.C. at 90°C (Ohm/km) Inductive reactance at 50Hz (Ohm/Km)
1 Conductor (1) 1 Conductor (2) 1 Conductor (3) Multiconductor (4) 4 Conductors (5)
2.57.9810.18------0.0930.1
44.956.31------0.0880.095
63.34.21------0.0830.09
101.912.44------0.0780.085
161.211.540.1390.1830.1250.0750.082
250.780.990.1270.170.1120.0750.083
350.5540.7070.1210.1650.1070.0730.081
500.3860.4930.1170.160.1020.0730.08
700.2720.3480.1120.1550.0970.0710.079
950.2060.2640.1070.1510.0930.070.077
1200.1610.2070.1050.1490.0910.070.077
1500.1290.1670.1030.1470.0890.070.077
1850.1060.1380.1020.1460.0880.070.077
2400.08010.1060.10.1430.0850.0690.077
3000.06410.0860.0980.1410.0830.0690.076
4000.04860.06750.0970.140.082----
5000.03840.05570.0960.1390.081----
6300.02870.04510.0940.1380.08----

(1) Three single conductor cables displayed in flat, in contact with each other. (2) Three single conductor cables displayed in flat, separated by 1 diameter between each other. (3) Three single-conductor cables displayed in a trefoil in contact with each other. (4) Calculation of Inductive reactance valid for two-conductor and three conductor cables. (5) Calculation of Inductive reactance valid for four-conductor cables.

Intensity of admissible currents

Nominal cross-section sq (mm²) Current-carrying capacity of cables in free air at 40°C as per IEC 364-5-523. Single-conductors cable up to 16mm² in contact with each other, displayed in unperforated trays, remaining cross-sections, single-conductors displays and formations in cable ladder or perforated cable trays. (Ampere) Current-carrying capacity of cables directly buried at 25°C soil temperature and soil thermal resistance of 1 km/W as per IEC 364-5-523. (Ampere)
1 Conductor (1) 1 Conductor (2) 1 Conductor (3) 2 Conductors Multiconductor (4) 1 Conductor (1) 1 Conductor (2) 2 Conductors Multiconductor (4)
2.5------3128----4437
4------4336----5748
6------5447----7261
10------7465----9783
1683----10086121129129107
25122158117128109157168166141
35152196146160137188201200168
50187238179195166220236238199
70241305232250213271290292243
95295371283304257326349351293
120346432332354299371396399333
150401499384409345415444448373
185461572441468394470503508425
240548675524554465547586592493
300637780608640537621665669559
400751938712----710759----
5008631083818----825882----
6309951257941----9411007----

(1) Three single conductor cables displayed in flat, in contact with each other. (2) Three single conductor cables displayed in flat, separated by 1 diameter between each other. (3) Three single-conductor cables displayed in a trefoil in contact with each other. (4) The values of current-carrying capacity informed, correspond to three-conductor, four-conductor.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x cross-section (mm²) Diameter under armour mm External diameter mm Weight kg/km Code
1x1610.014.4349EF 1160 D
1x2510.014.4402EF 1250 D
1x3511.115.5507EF 1350 D
1x5012.717.1660EF 1500 D
1x7014.619.2876EF 1700 D
1x9516.020.61077EF 1950 D
1x12018.222.81374EF 11200 D
1x15020.725.51688EF 11500 D
1x18523.027.82036EF 11850 D
1x24025.630.62602EF 12400 D
1x30029.034.23193EF 13000 D
1x40032.738.14153EF 14000 D
1x50037.242.85352EF 15000 D
1x63040.746.76704EF 16300 D
2x410.013.8319EF 0240 F
2x610.814.6372EF 0260 F
2x1012.616.4499EF 2100 F
2x1614.718.5668EF 2160 F
2x2518.021.8948EF 2250 F
2x3520.324.11210EF 2350 F
2x5023.527.31600EF 2500 F
2x7027.231.22139EF 2700 F
2x9530.534.72692EF 2950 F
2x12034.840.43868EF 21200 F
2x15039.945.94804EF 21500 F
2x18544.750.95853EF 21850 F
2x24050.056.47351EF 22400 F
2x30057.163.79115EF 23000 F
3x2.510.013.8313EF 0325 F
3x410.314.1349EF 0340 F
3x611.515.3431EF 0360 F
3x1013.417.2592EF 3100 F
3x1615.719.5810EF 3160 F
3x2519.223.01165EF 3250 F
3x3521.725.51508EF 3350 F
3x5025.229.02015EF 3500 F
3x7029.633.62751EF 3700 F
3x9532.737.13455EF 3950 F
3x12037.443.24902EF 31200 F
3x15043.349.56128EF 31500 F
3x18548.154.57414EF 31850 F
3x24054.260.89447EF 32400 F
3x30061.468.411648EF 33000 F
4x2.510.013.8321EF 0425 F
4x411.315.1405EF 0440 F
4x612.616.4507EF 0460 F
4x1014.818.6708EF 4100 F
4x1617.321.1980EF 4160 F
3x25+1x1620.324.11312EF 2516 F
3x35+1x1622.426.21636EF 3516 F
3x50+1x2526.330.12228EF 5025 F
3x70+1x3530.835.03056EF 7035 F
3x95+1x5034.440.04267EF 9550 F
3x120+1x7039.445.45540EF 12070 F
3x150+1x7044.450.66666EF 15070 F
3x185+1x9549.355.78104EF 18595 F
3x240+1x12055.862.610413EF 240120 F
3x300+1x15063.570.512811EF 300150 F