Aluminum tape interlock armour
Control, signalling, measuring and protective equipment, electric controls of mining, industrial and petrochemical projects For dry and wet locations, fixed on trays, indoors or outdoors, buried in ducts or directly buried. Suitable for mobile installations at low temperatures Manufactured in compliance with the Canadian Electrical Code CEC
Standard | ||
---|---|---|
Sheath | Conductors | |
1 Conductor | ||
2 Conductors | ||
3 Conductors | ||
4 Conductors | ||
5 Conductors (=>) | alphanumeric identification |
The information provided corresponds to the standard version. Alternative interlock armour (made of galvanized steel tape) can be manufactured upon request
Gauge AWG | Electrical resistance at 20°C in C.C. (Ohm/km) | Electrical resistance at 90°C in C.A. at 60Hz (Ohm/km) | Current-carrying capacity (1) | ||||||
---|---|---|---|---|---|---|---|---|---|
2x | 4x | 7x | 10x | 19x | 30x | 37x | |||
14 | 8.79 | 11.21 | 25 | 20 | 17.5 | 12.5 | 12.5 | 11.3 | 10 |
12 | 5.54 | 7.06 | 30 | 24 | 21 | 15 | 15 | 13.5 | 12 |
10 | 3.48 | 4.44 | 40 | 32 | 28 | 20 | 20 | 18 | 16 |
(1) Current-carrying capacity of cables with up to three conductors, installed in ducts or directly buried, up to an ambient temperature of 30ºC, according to chart 310.15 (B)(16) of the NFPA 70. As from four-conductors, we’ve additionally applied the correction factor for more than three conductors from the chart 310.15 (B)(3)(a) of the NFPA70.
Cable formation | Diameter below armour mm | Diameter under armour mm | External diameter mm | Weight kg/ km | Code | |
---|---|---|---|---|---|---|
Fase conductor | Bonding conductor (1) | |||||
N° Cond. x gauge AWG/MCM | Gauge AWG | |||||
2 x 14 | 14 | 9.6 | 16.4 | 19.4 | 360 | TKC 0214 |
3 x 14 | 14 | 10.8 | 17.7 | 20.7 | 411 | TKC 0314 |
4 x 14 | 14 | 12.0 | 19.0 | 22.0 | 463 | TKC 0414 |
5 x 14 | 14 | 12.0 | 19.0 | 22.0 | 490 | TKC 0514 |
6 x 14 | 14 | 12.7 | 19.6 | 22.6 | 531 | TKC 0614 |
7 x 14 | 3 x 18 | 14.5 | 21.5 | 24.5 | 619 | TKC 0714 |
9 x 14 | 14 | 17.0 | 24.1 | 27.1 | 713 | TKC 0914 |
12 x 14 | 14 | 18.2 | 25.3 | 28.3 | 821 | TKC 1214 |
15 x 14 | 14 | 20.2 | 27.9 | 30.9 | 1027 | TKC 1514 |
19 x 14 | 3 x 18 | 23.9 | 31.7 | 34.7 | 1273 | TKC 1914 |
25 x 14 | 14 | 25.1 | 32.9 | 35.9 | 1466 | TKC 2514 |
30 x 14 | 14 | 27.6 | 35.5 | 38.5 | 1663 | TKC 3014 |
37 x 14 | 3 x 18 | 30.1 | 38.0 | 41.0 | 1921 | TKC 3714 |
2 x 12 | 14 | 10.2 | 17.1 | 20.1 | 399 | TKC 0212 |
3 x 12 | 14 | 11.4 | 18.3 | 21.3 | 463 | TKC 0312 |
4 x 12 | 14 | 12.7 | 19.6 | 22.6 | 528 | TKC 0412 |
5 x 12 | 14 | 13.3 | 20.2 | 23.2 | 580 | TKC 0512 |
6 x 12 | 14 | 15.2 | 22.1 | 25.2 | 679 | TKC 0612 |
7 x 12 | 3 x 16 | 17.0 | 24.1 | 27.1 | 765 | TKC 0712 |
9 x 12 | 14 | 18.2 | 25.3 | 28.3 | 859 | TKC 0912 |
12 x 12 | 14 | 20.2 | 27.9 | 30.9 | 1109 | TKC 1212 |
15 x 12 | 14 | 22.7 | 30.4 | 33.4 | 1328 | TKC 1512 |
19 x 12 | 3 x 16 | 26.4 | 34.2 | 37.2 | 1603 | TKC 1912 |
25 x 12 | 14 | 27.6 | 35.5 | 38.5 | 1859 | TKC 2512 |
30 x 12 | 14 | 30.1 | 38.0 | 41.0 | 2122 | TKC 3012 |
37 x 12 | 3 x 16 | 33.8 | 41.8 | 44.8 | 2513 | TKC 3712 |
2 x 10 | 12 | 11.4 | 18.3 | 21.3 | 476 | TKC 0210 |
3 x 10 | 12 | 12.7 | 19.6 | 22.6 | 558 | TKC 0310 |
4 x 10 | 12 | 14.5 | 21.5 | 24.5 | 677 | TKC 0410 |
5 x 10 | 12 | 15.2 | 22.1 | 25.2 | 753 | TKC 0510 |
6 x 10 | 12 | 17.0 | 24.1 | 27.1 | 842 | TKC 0610 |
7 x 10 | 3 x 16 | 17.0 | 24.1 | 27.1 | 906 | TKC 0710 |
9 x 10 | 12 | 21.4 | 29.1 | 32.1 | 1211 | TKC 0910 |
12 x 10 | 12 | 23.9 | 31.7 | 34.7 | 1500 | TKC 1210 |
15 x 10 | 12 | 25.1 | 32.9 | 35.9 | 1712 | TKC 1510 |
19 x 10 | 3 x 16 | 27.6 | 35.5 | 38.5 | 2014 | TKC 1910 |
25 x 10 | 12 | 31.3 | 39.3 | 42.3 | 2475 | TKC 2510 |
30 x 10 | 12 | 35.1 | 43.1 | 46.1 | 2867 | TKC 3010 |
37 x 10 | 3 x 16 | 36.0 | 44.4 | 47.4 | 3416 | TKC 3710 |
(1) For 7, 19 and 37-conductor cables, the bonding is divided in three conductors. For the remaing formations, it is gathered in only one conductor together with the phases.