series UP

600 Volt
Cu 14 AWG up to 500 MCM
THW-2
UL 1277

Fixed power distribution networks in factories, warehouses, machine rooms, power distribution stations. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. Manufactured in compliance with the National Electrical Code ANSI/NFPA 70 of the US and the National Electrical Code NOM-001 SEDE, Mexico.

Features

  • Temperature ratings: 90°C (Operating) – 160°C (Short-Circuit)

  • Voltage rating: 600 V A.C.

  • Construction requirements: As per UL 1277

  • Conductor requirements: As per ASTM B8

  • Conductor: Annealed electrolytic copper conductor, class B stranding

  • Insulation: PVC type THW-2

  • Sheath: Flame retardant PVC

  • Fire requirements: As per UL 1685

  • Outdoors requirements: As per UL 2556 (UV Resistance)

  • NEC Code (NFPA 70): Art. 725 PLTC – Art. 727 ITC – Art. 800 CM – Art. 501 classified areas CL1 Div.2 y Cl2 Div.2

Fire-retardant

Fire-retardant

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Industrial applications

Industrial applications

NEC cod

NEC cod

Tray cable

Tray cable

Identification

Standard
Sheath Conductors
Multiconductor alphanumeric identification

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version. Upon request, we can supply cables with different alternatives of identification, cable flexibility, or also including additional shield for suitable electromagnetic protection.

ELECTRICAL CHARACTERISTICS

Resistances, reactance and intensity of admissible currents

Conductor’s gauge (AWG) Semi-rigid stranded conductor. Electrical Resistance in D.C. at 20ºC (Ohm/km) Semi-rigid stranded conductor. Electrical resistance in C.C. at 75°C (Ohm/km) Inductive reactance at 60Hz (Ohm/Km) Current-carrying capacity (6)
1 Conductor (1) 1 Conductor (2) 1 Conductor (3) Multiconductor (4) 4 Conductors (5)
1 Conductor Multiconductor 1 Conductor Multiconductor
148.628.7910.4810.690.1730.2260.1560.1170.12620
125.435.546.606.740.1620.2140.1450.1100.11825
103.413.484.154.230.1520.2040.1340.1030.11235
82.142.192.612.660.1500.2020.1330.1080.11750
61.351.371.641.670.1470.1990.1290.1100.11965
40.8480.8651.031.050.1380.1900.1200.1030.11285
20.5340.5440.6490.6620.1300.1820.1130.0980.106115
10.4230.4310.5150.5250.1350.1880.1180.1020.110130
1/00.3350.3420.4090.4170.1310.1840.1140.0990.107150
2/00.2660.2710.3250.3310.1280.1800.1100.0960.105175
3/00.2110.2150.2580.2630.1240.1770.1070.0940.103200
4/00.1670.1710.2060.2100.1210.1730.1040.0920.100230
2500.1420.1440.1750.1780.1250.1770.1080.0930.102255
3000.1180.1200.1460.1490.1230.1750.1050.0920.100285
3500.1010.1030.1260.1290.1200.1730.1030.0900.099310
4000.08850.09030.1120.1140.1190.1710.1010.0890.098335
4500.07870.08020.1000.1020.1170.1700.1000.0880.097355
5000.07080.07220.09130.09310.1160.1680.0990.0880.096380

(1) Three single conductor cables displayed in flat, in contact with each other. (2) Three single conductor cables displayed in flat, separated by 1 diameter between each other. (3) Three single-conductor cables displayed in a trefoil in contact with each other. (4)  Calculation of Inductive reactance valid for two-conductor, three-conductor, and five-conductor cables. (5) Calculation of Inductive reactance valid for four-conductor cables. (6) Current-carrying capacity of cables with up to three conductors, installed in ducts or directly buried, up to an ambient temperature of 30ºC, according to chart 310.15 (B)(16) of the NFPA 70. As from four-conductors, we’ve additionally applied the correction factor for more than three conductors from the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable formation N° Cond. x gauge AWG External diameter mm Weight kg/km Code
1x145,651UP 0114
2x149,0122UP 0214
3x149,5148UP 0314
4x1410,4180UP 0414
5x1411,4214UP 0514
1x126,166UP 0112
2x1210,0161UP 0212
3x1210,6198UP 0312
4x1211,6244UP 0412
5x1212,7292UP 0512
1x106,790UP 0110
2x1011,2219UP 0210
3x1011,9275UP 0310
4x1013,1342UP 0410
5x1015,1436UP 0510
1x88,2136UP 0108
2x814,9371UP 0208
3x815,9463UP 0308
4x817,4573UP 0408
5x819,1687UP 0508
1x69,9208UP 0106
2x618,4572UP 0206
3x619,6718UP 0306
4x622,6943UP 0406
5x624,71129UP 0506
1x411,2295UP 0104
2x424,1963UP 0204
3x425,51194UP 0304
4x427,91469UP 0404
5x430,31753UP 0504
1x212,7425UP 0102
2x227,11317UP 0202
3x228,81661UP 0302
4x231,52063UP 0402
5x234,42478UP 0502
1x115,4567UP 0101
2x131,11688UP 0201
3x133,12123UP 0301
4x136,32637UP 0401
5x139,83168UP 0501
1x1/016,5688UP 11/0
2x1/033,32009UP 21/0
3x1/035,42549UP 31/0
4x1/038,93181UP 41/0
5x1/044,23979UP 51/0
1x2/017,7832UP 12/0
2x2/035,62387UP 22/0
3x2/037,93051UP 32/0
4x2/041,73823UP 42/0
5x2/048,14855UP 52/0
1x3/0191012UP 13/0
2x3/038,22856UP 23/0
3x3/040,73678UP 33/0
4x3/047,14858UP 43/0
5x3/051,65853UP 53/0
1x4/020,41229UP 14/0
2x4/041,13425UP 24/0
3x4/045,44587UP 34/0
4x4/050,75846UP 44/0
5x4/055,67060UP 54/0
1x25023,41511UP 1250
2x25047,24305UP 2250
3x25050,35522UP 3250
4x25055,46927UP 4250
5x25060,88372UP 5250
1x30024,71762UP 1300
2x300504959UP 2300
3x30053,36396UP 3300
4x30058,78046UP 4300
5x30064,49740UP 5300
1x350262019UP 1350
2x35052,65625UP 2350
3x35056,17287UP 3350
4x35061,89188UP 4350
5x35067,911138UP 5350
1x40027,22265UP 1400
2x400556267UP 2400
3x40058,78146UP 3400
4x40064,76912UP 4400
1x50029,32738UP 1500
2x50057,16888UP 2500
3x50063,29780UP 3500
4x50071,38484UP 4500